Table 3, Solid State, Connection Sizes, Disconnect & Circuit Breaker
50/60 HZ
Max RLA
Incoming Size
Disc. Switch
Incoming Size
Circuit Breaker
74 #6- 350 #6- 350
93 #6- 350 #6- 350
148 #6- 350 #6- 350
163 #6- 350 #6- 350
185 2/C 3/0 - 500 2/C 3/0 - 500
296 2/C 3/0 - 500 2/C 3/0 - 500
444 3/C 1/0 - 500 3/C 1/0 - 500
593 4/C 250 - 500 4/C 250 - 500
889 5/C 300 - 600 5/C 300 - 600
1185 5/C 300 - 600 5/C 300 - 600
1481 5/C 300 - 600 5/C 300 - 600
NOTES:
1. For field wiring free-standing starters, the outgoing connection size is determined by
the starter size as listed under the “Outgoing Connection Size” column in Table 2.
Outgoing connections are factory-connected to the motor on factory-mounted starters.
2. When wiring to a starter (either factory-mounted or free-standing) with an optional
disconnect switch or circuit breaker, the incoming connection size is determined by the
device size as shown in the above table. For standard power block, the incoming
connections are as shown in Table 2.
Low Voltage Wye-Delta
Table 4, Wye-Delta Connection Sizes, Standard Power Block
Starter
Model No
(Note 1).
Incoming
Connection Size,
Power Block
Outgoing
Connection Size
(Note 2)
D3WD11 2/C #6 - 300 0.31
D3WD12 2/C #6 - 300 0.31
D3WD14 2/C #6 - 300 0.31
D3WD15 2/C #6 - 300 0.31
D3WD25 2/C #6 - 300 0.31
D3WD31 2/C #6 - 300 0.38
D3WD34 2/C #6 - 300 0.38
D3WD43 2/C #6 - 300 0.44
D3WD62 2/C #6 - 350 0.44
D3WD65 2/C #6 - 350 0.44
D3WD86 4/C 1/0 - 750 0.63
D3WD1K 4/C 1/0 - 750 0.63
D3WD2K 4/C 1/0 - 750 0.63
NOTES:
1. Data is the same for unit-mounted starters, D3WT11, etc.
2. Outgoing connection is NEMA 1 hole pattern, diameter in inches as shown.
3. Outgoing connections are factory-connected to the motor on factory-mounted starters.
4. When connecting to a power block, the connection size is determined by the starter size.