IOMM Starter 31
Display Operation
ispla
• View parameters, messages and faults.
• Shows software revision on power up.
amming
• Press PARAM to enter the menu and
then UP or DOWN to reach the desired
parameter.
• Press ENTER to show the present value
of the parameter.
• Press UP or DOWN to change the
parameter value.
• Press ENTER to store the new value or
PARAM to abandon the change.
Meters
• Press DOWN to display the motor
thermal overload content.
• Press UP to display the incoming line
phase order.
• Press ENTER to display the status
meter.
Log
• Press PARAM, Select P24 and press
ENTER. The most recent fault will be
displayed as “xFyy” where x will be 1
to indicate the most recent fault is
being displayed and yy is the fault
code.
• Press DOWN to view older faults. Up
to 9 faults may be stored in the log.
ting a Fault
• First correct the cause of the fault.
Then press RESET to reset from a
fault.
ting Parameters
• Press and hold PARAM and ENTER on
power up to reset parameters to
default values.
gency Thermal Reset
• Press RESET and DOWN to perform an
emergency thermal reset.