preclude it as a potenal source of moisture collecon. However, whether installed with
or without conduit, all cables should be examined for nicks and cuts that compromise the
protecve outer jackeng. In parcular, mul-conductor cables can act as very eecve
wicks when the outer jacket has been cut or damaged. Once moisture ingresses into the
cable, it will oen nd its way into the switch via this wicking mechanism, even when an
appropriate gland seal is used at the switch’s conduit opening and the outer periphery of
the cable is not leaking at the gland.
2.11.3 Liberally Apply Silicone Dielectric Grease to all Openings
The primary points of moisture entry into the switch are where the housing is penetrated:
- The setpoint adjustment screw (5550 only)
- The reset plunger (5550 only)
- The conduit ng(s)
- The seal between housing body and housing cover
O-ring seals and gaskets are used at each of these entry points and silicone dielectric
grease is applied at the factory. However, in extremely moist environments an addional
liberal coang of silicone dielectric grease should be applied in the eld at me of
installaon. This pracce will provide added protecon against moisture ingression
over me. Metrix recommends Dow Corning #33 Molykote® Extreme Low Temperature
Silicone Grease or equivalent.
2.12 Outline Diagrams and Physical Dimensions
Refer to the Metrix product datasheet # 1004461, available at www.metrixvibraon.com
3. IMPORTANT SAFETY INFORMATION
3.1 General Safety Summary
Review the following safety precauons to avoid injury and prevent damage to this product
or any products connected to it.
• USE ONLY AS SPECIFIED
To avoid potenal hazards, use this product only as specied. Only qualied personnel
should perform installaon and removal procedures.
• CONNECT AND DISCONNECT PROPERLY
Do not connect or disconnect this product while it is connected to a live power source.
• GROUND THE PRODUCT
The housing of this product should be connected to earth ground. Before energizing the
product, ensure its housing is properly grounded.
• OBSERVE ALL TERMINAL RATINGS
To avoid re or shock hazard, observe all rangs and markings on the product. Consult
the individual secons of this manual for further informaon before making connecons
to the product.
• DO NOT OPERATE WITHOUT COVER
The cover serves mulple purposes that may include protecon against moisture and
dust ingression, protecon of personnel from electrical shock, and protecon against