Troubleshooting
Page 86
5.2 E0/F4/EA (EEPROM parameter error)
Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip.
Recommended parts to prepare:
Indoor PCB
Outdoor PCB
Troubleshooting and repair:
Shut off the power supply and turn it
on 2 minutes later.
Is it still displaying the error
code?
The unit is operating normally.
NO
If the EEPROM chip is welded on main
PCB, replace the main PCB directly.
Otherwise, check if the EEPROM chip
plugged in main PCB well.
YES
Is it plugged well?
Correct the connection.
NO
Replace the indoor/outdoor
main PCB.
Remarks:
The location of the EEPROM chip on the indoor and outdoor PCB is shown in the following two images:
Note: These images are for reference only.