Outdoor Unit Disassembly 49
3.7 Compressor
WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the
four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the
system with nitrogen; then repeat the two steps before heating up the brazed parts. The operations above should be
implemented by professionals.)
Note: Remove the panel plate, connection of compressor on PCB (refer to 3.1 Panel plate and 3.2 Electrical
parts) before disassembling sound blanket.
Procedure Illustration
1) Remove the flange nut of terminal cover
and remove the terminal cover (see CJ_
ODU_COMP_001).
2) Disconnect the connectors (see CJ_ODU_
COMP_002).
CJ_ODU_COMP_001
CJ_ODU_COMP_002
Note: This section is for reference only. Actual unit appearance may vary.
Terminal Cover