V6 VRF 50Hz
38
Midea V6 Series Service Manual
5 Normal Operation Control
5.1 Component Control during Normal Operation
Table 3-5.1: Component control during normal cooling operation
Control functions and states
Controlled according to load requirement
Controlled according to discharge pressure
Electronic expansion valve
A
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to discharge
temperature
Electronic expansion valve
B
Electronic expansion valve
C
Position (steps) from 0 (fully closed) to 480 (fully
open), controlled according to temperature
different between plate heat exchanger inlet and
outlet
Solenoid valve (oil balance)
Solenoid valve (fast
defrosting (in heating) and
unloading (in cooling))
Controlled according to ambient temperature,
discharge pressure, discharge temperature,
compressor running frequency and discharge
superheat
Solenoid valve (EXV
bypass)
Controlled according to discharge pressure and
discharge temperature
Solenoid valve (indoor
units bypass)
Controlled according to load requirement
Solenoid valve (inverter
compressor A vapor
injection)
Controlled according to inverter compressor A
on/off
Solenoid valve (inverter
compressor B vapor
injection)
Controlled according to inverter compressor B
on/off
Solenoid valve (inverter
compressor B pressure
balance)
Open before compressor B startup and close after
compressor B running for 15 seconds. Open after
compressor B stop 10 seconds and keep open 60
seconds.