EasyManuals Logo
Home>Midea>Air Conditioner>V6 Series

Midea V6 Series User Manual

Midea V6 Series
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #75 background imageLoading...
Page #75 background image
V6 VRF 50Hz
74
Midea V6 Series Service Manual
2.3 E1: Phase sequence error
Digital display output 2.3.1
Description 2.3.2
Phase sequence error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition 2.3.3
Trigger condition: Wrong phase connection for 1.6s or phase missing for 48s.
Recover condition: Correct phase connection.
Reset method: Manually restart.
Possible causes 2.3.4
Power supply phases not connected in correct sequence.
Power supply terminals loose.
Power supply abnormal.
Main PCB damaged.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Midea V6 Series and is the answer not in the manual?

Midea V6 Series Specifications

General IconGeneral
BrandMidea
ModelV6 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals