2.1 Specifications
Models
Nominalcoolingcapacity*1
kW
22.4 28.0
Nominalheatingcapacity*2 25.0 31.5
Powersource
Powerconsumption
Cool
kW
5.60 8.09
Heat 6.03 8.21
Runningcurrent
Cool
A
9.25/8.47 13.22/12.10
Heat 9.85/9.02 13.41/12.28
SoundPressureLevel(Cool/Heat dB(A 58/58 59/60
Exteriordimensions
Height×Width×Depth
mm
Netweight kg 224
Refrigerantequipment
compressortype&Q'ty
GTC5150NH40K×1 GTC5150NH40K×1
Motor kW 3.81 5.22
Startingmethod
capacitycontrolrange % 27-114 20-115
Crankcaseheater W
Refrigerantequipment
Heatexchanger
Refrigerantcontrol
Refrigerant
Quantity kg
Refrigerantoil l
Defrostcontrol
Airhandlingequipment
fantype&Q'ty
Motor W
Startingmethod
Airflow(Standard CMM
Shock&vibrationabsorber
safetyequipment
Installationdata LiquidLine
Refrigerantpipingsize
GasLine
mm(in
Connectingmethod
Drain
Insullationforpiping
Accessories
Exteriorappearance
(Munsellcolor
FDCR224KXE6 FDCR280KXE6
connectablecapacity % 50-130 50-130
StaticPressure Pa
1675×1080×480
Directlinestart
33
Straightfin&innergroovedtubing
Electronicexpansionvalve
R410A
11.5
1.7(M-MA32R
MCcontrolledDe-Icer
Propellerfan× 2
144×2
Directlinestart
200
Rubbermount(forcompressor
LiquidFlare/GasBrazing
Holefordrain
φ
20×4)
Necessary(bothLiquid&Gaslines
stuccowhite
(4.2Y7.5/1.1nearequivalent
Max.35
380-415V3N〜50Hz
Compressorovercurrentprotection/abnormalhighpressureprotection
abnormallowpressureprotection/abnormaldischargetempertureprotection/overcurrentprotection
φ
9.52(3/8"
φ
15.88(5/8"
φ
19.05(3/4"
φ
25.4(1"
φ
22.22(7/8"
φ
28.58(11/8"
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling*1 27
:
19
:
35
:
24
:
ISO-T1
Heating*2 20
:
-
7
:
6
:
Notes (1) The data are measured at the following conditions. (The piping length is 7.5m)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) Refer to the technical data about below.
Reusability of the existing pipes.
Necessity of Re-fresh kit and Service valve kit when washing existing pipes.
Adapted to RoHS directive
PCB003Z361

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDCR224KXE6 and is the answer not in the manual?

Mitsubishi Heavy Industries FDCR224KXE6 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDCR224KXE6
CategoryHeat Pump
LanguageEnglish

Related product manuals