38
-
'11 • KX-T-166
6.3 Method for connecting the accessory pipe
Method for connecting the accessory pipe
Be sure to use the accessory pipe to connect the operation valve on the
gas side with the field pipe.
Table 1 Parts used for the connecting pipe assembly
Table 2 Length and specification of straight pipe (Procured in the field)
1
ReferringtoTable
1
andTable
2
,preparethestraightpipeandtheelbowintheeld,whichare
usedintheconstructionexamplesA-Dapplicabletotheconnectingdirection.
2
Firstly,usetheaccessorypipetoassembletheconnectingpipeassemblyoutsidetheoutdoorunit.
Asshownintheguresofconstructionexamples
A
〜
D
applicabletotheconnectingdirection
(chaindoubledashedline),brazetheaccessorypipeandthepartspreparedintheabove 1 .
●Orienttheaccessorypipeaccordingtothedimensionsasshownin ofFig.1.
3
Afterassemblyoftheconnectingpipe,connectittotheoperationvalveonthegassideinsidethe
outdoorunit.
Tightentheflarenutwithappropriatetorque.
4
Afterconnectionoftheconnectingpipeassemblytotheoperationvalveonthegasside,brazethe
connectingpipeassemblyandtheeldpipe.
5 Afterthebrazing,insulateusingtheattachedheatinsulatingmaterialandbandasshownbyFig.2.
Ifnonitrogengasissupplled,alargeamountofimpurity(oxidizedlm)willbegenerated,
whichmayclogthecapillarytubeandtheexpansionvalve,resultinginfatalmalfunction.
Besuretousepipesof1/2Hmaterial,andwallthicknessabove1mm.(PressureresistanceofO-type
pipeisnotenough)
Selectandusethepipes,whichareprocuredintheeld,
accordingtothespecicationthatcorrespondstothe
outdoorunitcapacityasdescribedintheinstallationmanual.
Be sure to braze while supplying nitrogen gas.
About brazing
Name
Accessorypipe
Heatinsulatingmaterial
Band
Straightpipe
1
Straightpipe
2
Elbow
A
Downward
B
Forward
C
Rightward
D
Backward
No.
1
2
3
4
5
6
Quantity
1
1
2
1
1 or 0
1 or 0
Remark
Accessory
Accessory
Accessory
Procuredattheeld
Procuredattheeld(Notrequiredfordownwarddirection)
Procuredattheeld(Notrequiredfordownwarddirection)
Straight pipe
1
Straight pipe
2
Straightpipe
1
Straightpipe
2
270mmorover
—
70〜120mm
125mmorover
70〜120mm
125mmorover
70〜120mm
515mmorover
224
280
ø19.05-ø25.4
ø22.22-ø28.58
PSB012D917G
k
ø19.05 100~120N¡m
Accessorypipe
Accessorypipe
Accessorypipe
Accessorypipe
Internalfaceofbase
Operationvalveconnecting
positionatgasside
Band
Proper torque
(Accessory)
(Accessory)
Pipe specification
Heatinsulatingmaterial
Internalfaceofbase
(Procuredintheeld,
125mmormore)
Straightpipe
2
(Procuredintheeld,
125mmormore)
Straightpipe
2
(Procuredintheeld,
515mmormore)
Elbow,
procuredintheeld
Elbow,
procuredintheeld
Elbow,
procuredintheeld
Brazetherefrigerantpipehere.
Brazetherefrigerantpipehere.
Brazetherefrigerant
pipehere.
Brazetherefrigerant
pipehere.
Connection example of refrigerant pipe -
B
(Forward connection)
Connection example of refrigerant pipe -
D
(Backward connection)
Connection example of refrigerant pipe -
C
(Rightward connection)
Connectionexampleofrefrigerantpipe-
A
(Downwardconnection)
Heat insulating method
(Fig. 2)
Accessorypipex1pc
Heatinsulating
materialx1pc
Bandx2pcs
Heatinsulatingmaterialisattachedtotheaccessorypipewith
band.Wheninstallingtheheatinsulatingmaterial,cuttheband
andretrieveit.
Twopiecesofg.2bandforinstallationarefoundinabag.
40
67
(Procuredintheeld,
70-120mm)
Straightpipe
1
(Procuredintheeld,
70-120mm)
Straightpipe
1
(Procuredintheeld,
70-120mm)
Straightpipe
1
(Procuredintheeld,
270mmormore)
Accessory pipe position
(Fig. 1)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDCR224KXE6 and is the answer not in the manual?

Mitsubishi Heavy Industries FDCR224KXE6 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDCR224KXE6
CategoryHeat Pump
LanguageEnglish

Related product manuals