'21 • SRK-T-299
-
127
-
(b) Auto air outlet selection
(i) COOL, DRY operation
1) In case both lower and upper outlets operation is selected in Cooling or Dry
operation, both outlets will be kept for sixty minutes after the start or until
indoor temperature is below the setting point. And then the air outlet will change
to the upper outlet. That state will be maintained until switch is turned off.
2) In case both outlets operation with auto fan speed mode is selected, the upper
outlet will be kept for ten minutes after the start or until indoor temperature is
close to reaching the setting point . And then the air outlet will change to both
outlets in order to spread comfort air to every corner.
(ii) HEAT operation
1) In case both lower and upper outlets operation with auto fan speed mode is selected, the
lower outlet will be kept for twenty minutes after the start or until room temperature is
close to reaching the setting point . And then the air outlet will change to both outlets.
That state will be maintained until the switch is turned off.
2) Automatic adjustment of lower air outlet direction prevents stirring up of warm air
and keeps optimum comfort at oor level.
'09•SRK-DB-087D
(11) 3D auto operation (SRK series only)
(a)
(b)
Fan speed
(i)
(ii)
Cooling
Air flow selection
Operation mode
AUTO HI MED LO
Heating
Room temp. – Setting temp. >5°C
Room temp. – Setting temp.
5°C
Setting temp. – Room temp. >5°C Setting temp. – Room temp.
5°C
HIGH POWER AUTO
HI MED LO
HIGH POWER AUTO
<
=
<
=
Flap
Louver
Cooling
Up/down swing
Heating
Wide (Fixed)Center (Fixed)
Flap
Louver
Cooling Heating
Left/right swing
Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Flap
Louver
Cooling Heating
Wide (Fixed)
Flap
Louver
Cooling Heating
Horizontal blowing (Fixed) Slant forwardl blowing (Fixed)
Operation mode
Room temp. – Setting temp. 2°C
Setting temp. – Room temp. 2°C
Heating
Cooling
Air flow direction contorol
2°C < Setting temp.
– Room
temp. 5°C
2°C <
Room
temp.
Setting temp. 5°C
Room temp. – Setting temp. > 5°C
Setting temp. – Room temp. > 5°C
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
The control in 4) continues. Control returns to the control in 2). Control returns to the control in 1).
<
=
<
=
<
=
<
=
Wide (Fixed)
Flap
Louver
Horizontal blowing (Fixed)
1)
2)
3)
4)
5)
3
4
During cooling and heating (Including auto cooling and heating)
setting temp.
Up/down swing
Center (Fixed)
During DRY operation
room
Room Room
room

Table of Contents

Other manuals for Mitsubishi Heavy Industries FDTC25VH1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDTC25VH1 and is the answer not in the manual?

Mitsubishi Heavy Industries FDTC25VH1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDTC25VH1
CategoryAir Conditioner
LanguageEnglish

Related product manuals