'21 • SRK-T-299
-
308
-
Information to identify the model(s) to which the information relates to: If function includes heating: Indicate the heating season the
Indoor unit model name FDTC25VH1 information relates to. Indicated values should relate to one
Outdoor unit model name SRC25ZS-W2 heating season at a time. Include at least the heating season 'Average'.
Function(indicate if present) Average(mandatory) Yes
cooling Yes Warmer(if designated) Yes
heating Yes Colder(if designated) No
Item symbol value unit Item symbol value class
Design load Seasonal efficiency and energy efficiency class
cooling Pdesignc 2.50 kW cooling SEER 6.80 A++
heating / Average Pdesignh 2.40 kW heating / Average SCOP/A 4.00 A+
heating / Warmer Pdesignh 3.00 kW heating / Warmer SCOP/W 5.10 A+++
heating / Colder Pdesignh - kW heating / Colder SCOP/C - -
Declared capacity at outdoor temperature Tdesignh Back up heating capacity at outdoor temperature Tdesignh
heating / Average (-10℃) Pdh 2.40 kW heating / Average (-10℃) elbu - kW
heating / Warmer (2℃) Pdh 3.00 kW heating / Warmer (2℃) elbu - kW
heating / Colder (-22℃) Pdh - kW heating / Colder (-22℃) elbu - kW
Declared capacity for cooling, at indoor temperature 27(19)℃ and Declared energy efficiency ratio, at indoor temperature 27(19)℃ and
outdoor temperature Tj outdoor temperature Tj
Tj=35℃ Pdc 2.50 kW Tj=35℃ EERd 4.10 -
Tj=30℃ Pdc 1.90 kW Tj=30℃ EERd 5.90 -
Tj=25℃ Pdc 1.20 kW Tj=25℃ EERd 9.20 -
Tj=20℃ Pdc 1.10 kW Tj=20℃ EERd 13.10 -
Declared capacity for heating / Average season, at indoor Declared coefficient of performance / Average season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh 2.20 kW Tj=-7℃ COPd 2.56 -
Tj=2℃ Pdh 1.20 kW Tj=2℃ COPd 3.94 -
Tj=7℃ Pdh 0.90 kW Tj=7℃ COPd 5.25 -
Tj=12℃ Pdh 1.10 kW Tj=12℃ COPd 6.48 -
Tj=bivalent temperature Pdh 2.40 kW Tj=bivalent temperature COPd 2.44 -
Tj=operating limit Pdh 2.40 kW Tj=operating limit COPd 2.44 -
Declared capacity for heating / Warmer season, at indoor Declared coefficient of performance / Warmer season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=2℃ Pdh 3.00 kW Tj=2℃ COPd 2.76 -
Tj=7℃ Pdh 2.00 kW Tj=7℃ COPd 4.78 -
Tj=12℃ Pdh 1.10 kW Tj=12℃ COPd 6.48 -
Tj=bivalent temperature Pdh 3.00 kW Tj=bivalent temperature COPd 2.76 -
Tj=operating limit Pdh 3.00 kW Tj=operating limit COPd 2.76 -
Declared capacity for heating / Colder season, at indoor Declared coefficient of performance / Colder season, at indoor
temperature 20℃ and outdoor temperature Tj temperature 20℃ and outdoor temperature Tj
Tj=-7℃ Pdh - kW Tj=-7℃ COPd - -
Tj=2℃ Pdh - kW Tj=2℃ COPd - -
Tj=7℃ Pdh - kW Tj=7℃ COPd - -
Tj=12℃ Pdh - kW Tj=12℃ COPd - -
Tj=bivalent temperature Pdh - kW Tj=bivalent temperature COPd - -
Tj=operating limit Pdh - kW Tj=operating limit COPd - -
Tj=-15℃ Pdh - kW Tj=-15℃ COPd - -
Bivalent temperature Operating limit temperature
heating / Average Tbiv -10 ℃ heating / Average Tol -10 ℃
heating / Warmer Tbiv 2 ℃ heating / Warmer Tol 2 ℃
heating / Colder Tbiv - ℃ heating / Colder Tol - ℃
Cycling interval capacity Cycling interval efficiency
for cooling Pcycc - kW for cooling EERcyc - -
for heating Pcych - kW for heating COPcyc - -
Degradation coefficient Degradation coefficient
cooling Cdc 0.25 - heating Cdh 0.25 -
Electric power input in power modes other than 'active mode'
Annual electricity consumption
off mode Poff 7 W cooling Qce 129 kWh/a
standby mode Psb 7 W heating / Average Qhe 840 kWh/a
Pto(cooling)
14 W heating / Warmer Qhe 823 kWh/a
Pto(heating)
18 W heating / colder Qhe - kWh/a
crankcase heater mode Pck 0 W
Capacity control(indicate one of three options) Other items
Sound power level(indoor) Lwa 51 dB(A)
Sound power level(outdoor) Lwa 58 dB(A)
fixed No Global warming potential GWP 675
staged No Rated air flow(indoor) - 510
variable Yes Rated air flow(outdoor) - 1644
Contact details for obtaining
more information Mitsubishi Heavy Industries Air-Conditioning Europe, Ltd.
5 The Square, Stockley Park, Uxbridge, Middlesex, UB11 1ET,United Kingdom
Herikerbergweg 238, Luna ArenA, 1101 CM Amsterdam, Netherlands
kgCO2eq.
m
3
/h
m
3
/h
Name and address of the manufacturer or of its authorised representative.
RWA000Z281
B
(4) 4-way ceiling cassette type (FDTC)
Model FDTC25VH1