'21 • SRK-T-299
-
185
-
'09•SRK-DB-087D
Current cut
Compressor lock, Compressor wiring short-circuit, Compressor output is open phase,
Outdoor unit PCB is faulty, Service valve is closed, EEV is faulty, Compressor faulty.
Current safe stop
Overload operation, compressor
lock, overcharge
193.
SRC20, 25 : 4.428Ω (U-V, V-W, U-W) or more at 20ºC
SRC35 : 1.703Ω (U-V, V-W, U-W) or more at 20ºC
.
short-circuit?
unit
Defective outdoor unit PCB
Defective outdoor unit PCB
between terminals.
Inspect outdoor air temperature sensor.
Defective outdoor unit PCB