167
-
'18 • SCM-T-251
(1) Auto operation
(a)
If “Auto” mode is selected by the remote control, the heating and the cooling are automatically switched according to the
difference between outdoor air temperature and setting temperature and the difference between setting temperature and
return air temperature. (When the switching of cooling mode
heating mode takes place within 3 minutes, the compressor
does not operate for 3 minutes by the control of 3-minute timer.) This will facilitate the cooling/heating switching operation
in intermediate seasons and the adaptation to unmanned operation at stores, etc (ATM corner of bank).
Notes (1) Temperature range of switching cooling/heating mode can be changed by RC-EX3 from ±1.0
-
±4.0.
(2) Room temperature control during auto cooling/auto heating is performed
according to the room temperature setting temperature. (DIFF: ±1 deg)
(3) If the indoor heat exchanger temperature rises to 59°C or higher during
heating operation, it is switched automatically to cooling operation. In
addition, for 1 hour after this switching, the heating operation is not
performed, regardless of the temperature shown at right.
+3-3
Cooling operation
Heating operation
Room temperature (detected with Thi-A) [deg]
Room temperature setting temperature
5956
Heating operation stopped (cooling)
Heating OK
Indoor heat exchanger temperature (°C)
(b) The following automatic controls are performed other than (a) above.
 
(i) Cooling or heating operation mode is judged according to the conditions of the "Judgment based on Setting temperature
+ Cooling select temperature and Indoor return air temperature" and the "Judgment based on Outdoor temperature".
1)
In case of "Setting temperature - Cooling select temperature < Indoor return air temperature" and "Outdoor temperature/
Cooling < Outdoor air temperature"
Operation mode: Cooling
2)

In case of "Setting temperature + Heating select temperature > Indoor return air temperature" and "Outdoor
temperature/Heating > Outdoor air temperature"
Operation mode: Heating
3) The outdoor air temperature of the above judgment conditions is sampled at every 10 minutes.
4) In the range where the above cooling and heating zones are overlapped
Forced thermostat OFF
Indoor return air temperature ()
Outdoor air temperature ()
24 2612 14 16 18 28 3020 22
12
26
24
22
20
18
16
14
30
28
Heating
Cooling
Forced thermostat OFF
Forced thermostat
OFF
Forced
thermostat OFF
Outdoor temperature/Heating
Outdoor temperature/Cooling
Cooling select temperature Heating select temperature
Setting temperature
7.2.3 Operation control function by the indoor control

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM50ZS-S1 and is the answer not in the manual?

Mitsubishi Heavy Industries SCM50ZS-S1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM50ZS-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals