EasyManuals Logo
Home>Mitsubishi Heavy Industries>Air Conditioner>SCM50ZS-W

Mitsubishi Heavy Industries SCM50ZS-W User Manual

Mitsubishi Heavy Industries SCM50ZS-W
164 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
-
61
-
'19 • SCM-SM-281
(32) Fan circulator operation (RC-EX3A only)
When the fan is used for circulation, the unit is operated as follows depending on the setting with the remote control.
(a) If the invalid is selected with the remote control, the fan is operated continuously during the fan operation. (normal fan mode)
(b) If the valid is selected with the remote control, the fan is operated or stopped when on the difference of the remote
control temperature sensor and the return air temperature sensor becomes bigger than 3°C.
(33) The operation judgment is executed every 5 minutes (RC-EX3A only)
Setting temperature Ts is changed according to outdoor temperature.
This control is valid with cooling and heating mode. (Not auto mode)
(a) Operate 5 minutes forcedly.
(b) Setting temperature is adjusted every 10 minutes.
(i) Cooling mode.
Ts = outdoor temperature
offset value
(ii) Heating mode.
Ts = outdoor temperature
offset value
(c) If the return air temperature lower than 18°C in cooling or return air temperature becomes higher than 25°C in heating,
unit goes thermostat OFF.
(34) Auto fan speed control (RC-EX3A only)
In order to reach the room temperature to the set temperature as quickly as possible, the air ow rate is increased when the
set temperature of thermostat differs largely from the return air temperature. According to temperature difference between
set temperature and return air temperature, indoor fan tap are controlled automalically.
Auto 1: Changes the indoor fan tap within the range of Hi ↔ Me ↔ Lo.
Auto 2: Changes the indoor fan tap within the range of P-Hi ↔ Hi ↔ Me ↔ Lo.
(35) Indoor unit overload alarm (RC-EX3A only)
If the following condition is satised at 30 minutes after starting operation, RC-EX3A shows maintenance code "M07"
and the signal is transmitted to the external output (CnT-2-5).
Cooling, Dry, Auto(Cooling) : Indoor air temperature = Set room temperature by remote control + Alarm temperature difference
Heating, Auto(Heating) : Indoor air temperature = Set room temperature by remote control - Alarm temperature difference
Alarm temperature difference is selectable between 5 to 10°C.
If the following condition is satised or unit is stopped, the signal is disappeared.
Cooling, Dry, Auto(Cooling) : Indoor air temperature = Set room temperature + Alarm temperature difference -2°C
Heating, Auto(Heating) : Indoor air temperature = Set room temperature - Alarm temperature difference +2°C
(36) Peak-cut timer (RC-EX3A only)
Power consumption can be reduced by restricting the maximum capacity.
Set the [Start time], the [End time] and the capacity limit % (Peak-cut %).
4-operation patterns per day can be set at maximum.
The setting time can be changed by 5-minute interval.
The selectable range of capacity limit % (Peak-cut %) is from 0% to 40-80% (20% interval).
Holiday setting is available.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM50ZS-W and is the answer not in the manual?

Mitsubishi Heavy Industries SCM50ZS-W Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM50ZS-W
CategoryAir Conditioner
LanguageEnglish

Related product manuals