(7) Inverter failure diagnosis
If the results of the diagnosis in Item (3) indicate that the inverter is defective, perform the following inspection on the inverter.
(a) Diagnosis procedure
Is DC280V imposed between the
power transistor P and N?
Is there output at CNN, CNH on
the printed circuit bord (CPU)?
Is the voltage at U, V and W of
the power transistor?
Is the diode stack good?
Is condenser good?
Is there conducitvity in the inductor?
Is the fuse good?
Is the varistor good?
Is the noise filter good?
Fuse is defective
e Replace
Varistor is defective
e Replace
Noise filter is defective
e Replace
The printed circuit board
(CPU) is defective
e Replace
The printed circuit board
(POWER) is defective
e Replace
The power transistor is
defective e Replace
YES
YES
YES
YES
YES
YES
YES
Condenser is defective
e Replace
Inductor is defective
e Replace
The diode stack is defective
e Replace
YES
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
Inspect compressor

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SCM60ZF-S and is the answer not in the manual?

Mitsubishi Heavy Industries SCM60ZF-S Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSCM60ZF-S
CategoryAir Conditioner
LanguageEnglish

Related product manuals