- 56 -
Outdoor fan motor error (Failure of fan motor, failure of outdoor PCB)
(8) Actions in case of short circuit and wire break of sensor
(a) Indoor unit
Sensor
Operation type
Actions
Short circuit
Wire break
Room
temp.
sensor
Cooling
Become the compressor continuous
operation instruction
No compressor operation instruction
obtained
Heating
No compressor operation instruction
obtained
Become the compressor continuous
operation instruction
Heat
exchanger
sensor
Cooling
Usual operation of system is
possible.
No compressor operation instruction
obtained (frost prevention)
Heating
High pressure control mode
(inverter stop instruction)
Heat-retaining (stop of indoor fan)
Humidity
sensor
(1)
Cooling
in the table below
in the table below
Heating
Usual operation of system is possible.
Note: (1) Only Model 50 has a humidity sensor.
Actions of humidity sensor
Failure mode
Reading of
control input
circuit
Operation of air
conditioner
Wire
break
wire
break
Humidity
reading 0%
Operating in drying
mode
wire
break
Humidity
reading 0%
Operating in drying
mode
①② wire
break
Humidity
reading 0%
Operating in drying
mode
Short
circuit
and
short circuit
Humidity
reading 100%
Operating in cooling
mode
Note: Do not use an instrument for power-on inspection of the humidity
sensor. Accidents may occur if DC is applied.
(b) Outdoor unit
Sensor
Operation type
Actions
Short circuit
Wire break
Heat
exchanger
liquid pipe
sensor
Cooling
Usual operation of system is
possible.
Usual operation of system is
possible.
Heating
The defrosting does not function.
10 min. defrosting about once an
hour
Outdoor air
temp. sensor
Cooling
Usual operation of system is
possible.
Usual operation of system is
possible.
Heating
The defrosting does not function.
10 min. defrosting about once an
hour
Compressor
vent-pipe
sensor
All modes
Compressor over heat protection is
impossible. (The unit can run.)
The compressor stops. (The inverter
does not output.)
No
Is the connection of the connector
normal?
No
Yes
Correct the connector.
Has voltage been applied to the fan
motor?
Yes
Failure of outdoor PCB
Failure of fan motor
Humidity sensor element
Humidity sensor component
Joint

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries SRK20MA-S and is the answer not in the manual?

Mitsubishi Heavy Industries SRK20MA-S Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelSRK20MA-S
CategoryAir Conditioner
LanguageEnglish

Related product manuals