Serial signal transmission error (Wrong power supply and signal cable connection, failure of
indoor and outdoor PCB, error of power supply system)
Indoor fan motor error (Failure of fan motor, failure of indoor PCB)
Compressor lock (Failure of compressor, failure of outdoor PCB)
Is the power supply abnormal in
operation after reset?
Failure caused by one-time reason (noise,
etc.), not failure of machine
Is the indoor and outdoor
connection correct?
Correct the indoor and outdoor connection
Dose the voltage between indoor
terminal block 2~3 fluctuate
between DC 0V and about 12V?
Dose the voltage between outdoor
terminal block 2~3 fluctuate
between DC 0V and about 12V?
Is there AC voltage of
220/230/240V between outdoor
terminal block 1~2?
Failure of indoor PCB. Check the
connection.
Is the power supply system
(protective tube, choke, etc.) in
good condition?
Replace the protective tube, choke, etc.
Is the connection of the connector
normal?
Has voltage been applied to the fan
motor?
Has all three-phase output
voltage been applied to the power
transistor?
Visually inspect wiring of compressor
Check insulating resistor (above 1MΩ)
Check winding coil resistor (about several Ω)
In normal cases, the
compressor is locked.