4 - 9 4 - 9
MELSEC-Q
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
(2) Operating procedure
Perform settings, starting with the GX Developer I/O assignment screen.
(a) I/O assignment screen
Specify the following for the slot where the Q62HLC
is mounted.
Type : Select "Intelli."
Model name : Enter the module's model name.
Points : Select 16 points.
Start XY : Enter the start I/O signal for the
Q62HLC.
(b) Switch setting for I/O and intelligent function module
Click on Switch Setting
on the I/O assignment
screen to display the screen at left and set switches
1 to 5. The setting can easily be done if values are
entered in hexadecimal. Change the input format to
hexadecimal and enter values.
REMARK
You need not set the "error-time output mode" and "hardware error-time CPU
operation mode" in the intelligent function module detailed setting as they are invalid
for the Q62HLC.