4 - 8 4 - 8
MELSEC-Q
4 SETUP AND PROCEDURE BEFORE STARTING THE OPERATION
4.5 Switch Settings for the Intelligent Function Module
This section explains the intelligent function module switch settings.
Make intelligent function module switch settings in I/O assignment setting on GX
Developer.
Making intelligent function module switch settings allows you to set to the Q62HLC the
output status to be established when the programmable controller CPU has comes to
an error stop.
Refer to Section 3.2.12 for setting details.
(1) Setting items
Five switches (switch numbers 1 to 5) are available for the intelligent function
module and they are set with 16 bit data.
If the switches for the intelligent function module are not set, the default value of
0 is used for switches 1 to 5.
Setting items
Switch 1
H4
CH3 CH2 CH1
H
Output setting for CPU stop error
0 : CLEAR
Other than 0 : HOLD
Switch 2
*1
Control status when switching to program control
1 : Switch with executing control
Other than 1 : Switch with suspending control
Switch 3 Reserved (0 fixed)
Switch 4 Reserved (0 fixed)
Switch 5 Reserved (0 fixed)
1: Compatible with the Q62HLC of which the first five digits of the production
information is "10022" or later or the first five digits of the product information
is "10011" or later. (For the method of confirming the production information
and product information, refer to Section 2.3.)
When using the Q62HLC which is not compatible with this setting, set 0.