3 - 2 3 - 2
MELSEC-Q
3 OUTPUT MODULE SPECIFICATIONS
3.2 QY10-TS Contact Output Module
This module is a spring clamp terminal block type and an output module that has
indicators for checking the insertion state of wire.
Type
Specifications
Contact output module
QY10-TS Appearance
Number of output points 16 points
Isolation method Relay
Rated switching voltage,
current
24VDC 2A (resistive load)
240VAC 2A (cos =1)
/point, 8A/common
Minimum switching load 5VDC 1mA
Maximum switching load 264VAC 125VDC
Response
time
OFF to ON 10ms or less
ON to OFF 12ms or less
Life
Mechanical 20 million times or more
Electrical
Rated switching voltage/current load
100 thousand times or more
200VAC 1.5A, 240VAC 1A (COS =0.7) 100 thousand times or more
200VAC 0.4A, 240VAC 0.3A (COS =0.7) 300 thousand times or more
200VAC 1A, 240VAC 0.5A (COS =0.35) 100 thousand times or more
200VAC 0.3A, 240VAC 0.15A (COS =0.35) 300 thousand times or more
24VDC 1A, 100VDC 0.1A (L/R=7ms) 100 thousand times or more
24VDC 0.3A, 100VDC 0.03A (L/R=7ms) 300 thousand times or more
Maximum switching
frequency
3600 times/hour
Surge suppressor No
Fuse No
Dielectric withstand voltage 2830VAC rms/3 cycles (altitude 2000m)
Insulation resistance 10M or more by insulation resistance tester
Noise immunity
By noise simulator of 1500Vp-p noise voltage, 1 s noise width
and 25 to 60Hz noise frequency
First transient noise IEC61000-4-4: 1kV
Protection degree IP2X
Common terminal
arrangement
16 points/common (common terminal: TB17)
Number of occupied I/O
points
16 points (I/O assignment is set as a 16-point output module.)
Operation indicator ON indication (LED)
External connections Two-piece spring clamp terminal block
Applicable wire size
0.3 to 2.0mm
2
core (22 to 15 AWG)
Applicable crimping terminal Refer to section 9.1
Internal current consumption
(5VDC)
430mA (TYP. all points ON)
Weight 0.22kg
External connection Terminal block No. Signal name
TB1 Y00
TB2 Y01
TB3 Y02
TB4 Y03
TB5 Y04
TB6 Y05
TB7 Y06
TB8 Y07
TB9 Y08
TB10 Y09
TB11 Y0A
TB12 Y0B
TB13 Y0C
TB14 Y0D
TB15 Y0E
TB16 Y0F
TB17 COM
TB18 Vacant
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
18
17
0
8
1
9
2
A
3
B
4
C
5
D
6
E
7
F
QY10-TS
11
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi QX10 and is the answer not in the manual?

Mitsubishi QX10 Specifications

General IconGeneral
BrandMitsubishi
ModelQX10
CategoryController
LanguageEnglish

Related product manuals