Page #83 background imageLoading...
Page #83 background image
3 - 7 3 - 7
MELSEC-Q
3 OUTPUT MODULE SPECIFICATIONS
3.6 QY40P-TS Transistor Output Module (Sink Type)
This module is a spring clamp terminal block type and an output module that has
indicators for checking the insertion state of wire.
Type
Specifications
Transistor output module (Sink type)
QY40P-TS Appearance
Number of output points 16 points
Isolation method Photocoupler
Rated load voltage 12-24VDC (+20/-15%)
Maximum load current 0.1A/point, 1.6A/common
Maximum inrush current 0.7A, 10ms or less
Leakage current at OFF 0.1mA or less
Maximum voltage drop at ON 0.1VDC (TYP.) 0.1A, 0.2VDC (MAX.) 0.1A
Response time
OFF to ON 1ms or less
ON to OFF 1ms or less (rated load, resistive load)
Surge suppressor Zener diode
Fuse No
External supply
power
Voltage 12-24VDC (+20/-15%) (ripple ratio within 5%)
Current MAX. 10mA (when 24VDC and all points are ON)
Dielectric withstand voltage 560VAC rms/3 cycles (altitude 2000m)
Insulation resistance 10M or more by insulation resistance tester
Noise immunity
By noise simulator of 500Vp-p noise voltage, 1 s noise width
and 25 to 60Hz noise frequency
First transient noise IEC61000-4-4: 1kV
Protection degree IP2X
Common terminal arrangement 16 points/common (common terminal: TB18)
Number of occupied I/O points 16 points (I/O assignment is set as a 16-point output module.)
Protection function
Yes (overload protection function, overheat protection function)
• Overheat protection function is activated in increments of 1 point.
• Overload protection function is activated in increments of 1 point.
Operation indicator ON indication (LED)
External connections Two-piece spring clamp terminal block
Applicable wire size
0.3 to 2.0mm
2
core (22 to 15 AWG)
Applicable crimping terminal Refer to section 9.1
Internal current consumption
(5VDC)
65mA (TYP. all points ON)
(0.07A is shown on the rating plate of the module.)
Weight 0.16kg
External connection Terminal block No. Signal name
TB1 Y00
TB2 Y01
TB3 Y02
TB4 Y03
TB5 Y04
TB6 Y05
TB7 Y06
TB8 Y07
TB9 Y08
TB10 Y09
TB11 Y0A
TB12 Y0B
TB13 Y0C
TB14 Y0D
TB15 Y0E
TB16 Y0F
TB17 12/24VDC
TB18 COM
1
2
3
4
5
6
7
8
9
10
12
13
14
15
16
18
17
0
8
1
9
2
A
3
B
4
C
5
D
6
E
7
F
QY40P-TS
11