126
-
'11 • SCM-SM-110
Error code
Remote controller:
LED Green Red
Outdoor
Content
4 times flash
Indoor
Keeps flashing
Stays OFF
E45
Outdoor sub PCB
communication error
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
YES
Replace the outdoor main PCB.
NO
YES
YES
Is the connector
connection between the outdoor
main PCB and the outdoor sub
PCB OK?
Is the power supply voltage OK?
Is the
communication wire
between the main PCB and the outdoor sub
PCB connected properly?
Is normal state restored?
YES
NO
NO
NO
Correct connector.
Check why power is not
supplied to outdoor sub
PCB.
Connect communication
wire securely.
Defective outdoor sub PCB
Replace.
Malfunction by temporary
noise
2. Error detection method
Detected communication error
of more than 15 seconds 4 times
in 15 minutes.
3.
Condition of Error displayed
When communication is not
established between the outdoor
sub PCB and the outdoor main
PCB.
4. Presumable cause
Defective sub PCB
Defective connector between
the outdoor main PCB and
outdoor sub PCB
Defective outdoor main
(control) PCB
Note:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM80ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM80ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM80ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals