44
-
'11 • SCM-SM-110
(9) Crankcase heater
(a) Operating conditions
(When all the conditions below are satisfied)
After the operation mode is changed to stop and the compressor command speed becomes 0 rps continuously for 30 minutes.
When the temperature detected by the outdoor air temperature (Tho-A) is 10°C or lower after the compressor stops.
(8) Freezing cycle system protective control
(a) Starting condition:
This control starts when the following conditions are met.
1)
 
When it has elapsed 30 minutes after the compressor was changed from OFF to ON in the cooling operation mode for
more than 5 minutes.
2)
 
When the compressor command speed has met the following conditions.
3)
 
When the indoor air temperature of running indoor unit (Th1) and the indoor heat exchanger temperature (Th2) have
met the following condition even on one unit.
Note (1) Values in ( ) are for the model SCM40, 45, 50.
(b) Contents of control
1)
 
Stop the compressor and delay the start, and then restarts.
2)
 
Compressor stops by the abnormal stop when the compressor stop has occurred 3 times in one hour.
Unit
Compressor
command speed
Indoor air temperature
(Th1,
)
Indoor air temperature (Th1) and indoor
heat exchanger temperature (Th2)
Duration
1
40 (60) rps
10
<
=
Th1
<
=
40
Th1 - 4 < Th2
5 minute
2
50 (70) rps
3
60 (80) rps Th1 - 3 < Th2
4
70 rps
Th1 - 2 < Th2
5
80 rps
6
90 rps
(b) Detail of operation
The crankcase heater operates, warming up the compressor, then refrigerant begins circulating smoothly when the cooler
starts its heating operation, and heating begins.
(c) Restoration conditions
When the temperature detected by the outdoor air temperature (Tho-A) reaches 12°C or higher, or the operation mode
changes from stop to cooling or heating.
(10) Inching prevention
When the compressor becomes to the thermo operation within 5 minutes since operation start or becomes dehumidifying opera
-
tion, the operation is continued with the compressor command speed of minimum rps forcibly.
(11) Compressor overheat protection
(a) Purpose:
(b) Detail of operation
1)
Discharge pipe temperature (˚C)
(Example) Fuzzy
95 105 115
3 minutes
3 minutes
3 minutes
105
115
95
105
95
105
3 minutes
3 minutes
Tho-D

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM80ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM80ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM80ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals