41
-
'11 • SCM-SM-110
1) Start condition:
When the high pressure sensor (HPS) has risen to a specified pressure while the compressor is
turned on.
2) Compressor command speed is controlled according to the zones of high pressure sensor as
shown by the following table.
HPS < P2
P2
<
=
HPS < P3 P3
<
=
HPS P4
<
=
HPS
Protection control speed (NP)
Normal Retention NP
8rps 0rps
Sampling time (s)
Normal 30 20 Normal
(a) Operating conditions:
When the outdoor air temperature (Tho-A) is 22°C or lower continues for 20 seconds while
compressor command
speed is other than 0 rps.
(b) Detail of operation:
The lower limit of compressor command speed is set to B or D rps and even if the speed becomes lower than B or D
rps, the speed is kept to B or D rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
The upper limit of compressor command speed is set to A or C rps, the speed is kept to A or C rps.
(c) Reset conditions:
When the either of the following condition is satisfied
When the outdoor air temperature (Tho-R) becomes 25°C or higher.
When the compressor command speed is 0rps.
(4) Cooling low outdoor temperature protective control
22 25
OFF
0 3
Upper limit C rps
Lower limit D rps
ON
ON
Upper limit A rps
Lower limit B rps
Outdoor air temperature.(°C)
Model
A
B
C
D
75 rps
35 rps
60 rps
45 rps
SCM40ZJ-S
75 rps
35 rps
60 rps
45 rps
SCM45ZJ-S
75 rps
35 rps
60 rps
45 rps
SCM50ZJ-S1
75 rps
30 rps
60 rps
40 rps
SCM60ZJ-S1
75 rps
30 rps
60 rps
40 rps
SCM80ZJ-S1
75 rps
30 rps
60 rps
40 rps
SCM71ZJ-S1
Model
A
B
C
D
75 rps
20 rps
60 rps
31 rps
SCM100ZJ-S1
75 rps
20 rps
60 rps
31 rps
SCM125ZJ-S1
Values of A ~ D
Model SCM100, 125
HPS
NP
P2 P3 P4
20
<
=
NP < 30
2.94 – 3.45 3.07 – 3.85 3.15 – 4.05
30
<
=
NP < 90
3.45 3.85 4.05
90
<
=
NP < 100
3.45 – 3.25 3.85 – 3.60 4.05 – 3.81
100
<
=
NP < 110
3.25 – 3.07 3.60 – 3.33 3.81 – 3.53
110
<
=
NP
3.07 3.33 3.53
Unit: MPa

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM80ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM80ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM80ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals