'11 • SCM-SM-110
(c) Current safe control value: Set this using the jumper wire (J1 or J2) on the outdoor PCB. Control starts
when it exceeds the control value.
1) Switching with jumper wire
Jumper wire (J2)
Short-circuit
(At shipping from factory)
Short-circuit
Jumper wire (J1)
Short-circuit (At shipping from factory) Current safe
Current safe
Open Current safe
Current safe
2) Control value
Model
Current safe
Current safe
Current safe
Cooling Heating Cooling Heating Cooling Heating
SCM40, 45ZJ-S, 50ZJ - S1
10.0 12.0 10.0 10.0 7.5 7.5
SCM60ZJ - S1
11.0 14.0 10.0 10.0 7.5 7.5
SCM71, 80ZJ - S1
13.0 16.0 10.0 10.0 7.5 7.5
Unit: A
2)
(12) Current safe
(a) Purpose:
(b) Detail of operation:
Cooling Heating
Lower limit speed
Item
Model
115
SCM40, 45, 50
SCM60, 71, 80, 100, 125
32 rps 32 rps
32 rps25 rps
Model SCM40, 45, 50, 60, 71, 80
Detecting the outdoor unit inverter input (primary) current and the output (secondary) current, if the current values exceed setting
values, the compressor speed (frequency) is controlled to protect the inverter.
Retention
Reduces frequency
at each minute.
Reset
B A
Current (A)
12
14
16
18
20
22
24
5040 60 70 80 90 100 110 120 130
Control or reset valve (A)
Compressor speed (frequency) (rps)
(Fig. C) The control value “A” and the reset value vary depending
on the compressor speed.
Reset valve B
Control valve A
Cooling Heating
Control
value A
Reset value
B
Control
value A
Reset value
B
Primary
current
side
21 20 23 20
Secandary
current
side
Fig.C Fig.C Fig.C Fig.C
Model SCM100, 125

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM80ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM80ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM80ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals