(b) Dew prevention control
Ⅱ
[Cooling]
Prevents dewing on the indoor unit.
(i) Operating conditions
When the following conditions have been satised for more than 30 minutes after starting operation
1) Compressor speed is 32 rps or higher. (SRK25, 35)
2) Humidity is 68% or higher. (SRK45 : 60%)
(ii) Contents of operation
1) Air capacity control
Note (1) Ranges A and B are as shown below.
2) When this control has continued for more than 30 minutes continuously,the following wind direction control is per-
formed.
a) When the vertical wind direction is set at other than the vertical swing,the aps change to the horizontal position.
b) When the horizontal wind direction is set at other than the horizontal swing,the louver changes to the vertical po-
sition.
(iii) Reset condition
When any of followings is satised.
1) Humidity is less than 63%. (SRK45 : 55%)
(12) Protection control function
(a) Dew prevention control
Ⅰ
[Cooling]
Prevents dewing on the indoor unit.
(i) Operating conditions
When the following conditions have been satised.
1) Humidity is 78% or higher.
(ii) Contents of operation
Maximum compressor speed
SRK25ZSP-W
68 rps
SRK35ZSP-W
73 rps
SRK45ZSP-W
87 rps
(iii) Reset condition
When either of the following condition is satised.
1) Humidity is 73% or less.
2) Dew prevention control
Ⅱ
has been satised.
Humidity(%)
68
73
Range A
Range B
Model
Item
SRK25,35ZSP-W SRK45ZSP-W
LO
Upper limit of compressor speed
RangeA: 41rps, RangeB: 41rps RangeA: 57rps, RangeB: 39rps
Indoor fan 4th speed (SRK35 : 5th speed)
AUTO,HI,MED
Upper limit of compressor speed
RangeA: 41rps, RangeB: 41rps RangeA: 57rps, RangeB: 39rps
Indoor fan
Adaptable to compressor
speed (Lower limit 4th speed)