Electrical connections
• Electrical installation and wiring must be carried out in
accordance with national provisions.
• Disconnect F2120 before insulation testing the house
wiring.
• If a miniature circuit breaker is used, this must have at
least triggering characteristic "C". See section "Technical
specifications" in the Installer Manual for F2120.
• If the building is equipped with an earth-fault breaker,
F2120 should be equipped with a separate one.
• F2120 must be installed via an isolator switch. The cable
area has to be dimensioned based on the fuse rating used.
The RCD should have a nominal tripping current of no
more than 30 mA. The incoming supply must be 400V 3N~
50Hz via an electrical distribution unit with fuses.
• The routing of cables for heavy current and signals should
be made out through the cable glands on the heat pump's
right-hand side, seen from the front.
• The communication cable must be a screened cable with
three conductors.
• Connect the charge pump to the control module. See
where the charge pump is to be connected in the Installer
Manual for your control module.