5
2.4. SPECIFICATIONS
Model
NE55
Power supply(V/Ph/Hz)
208-230V~/60Hz
Rated Ambient Temp Range (°F)
23~104
1
Heating Capacity (Btu/h) 80/80/80
55000
1
COP
6.0
2
Heating Capacity (Btu/h) - 50/63/80
35000
2
COP
4.0
Maximum Water Outlet Temp. (°F)
104
Rated Water Flow (gpm)
23.8
Rated Water Pressure Drop (psi)
3.77
Maximum Input Power (kBtu/h)
14.0
Fan Motor Rating Load (FLA) (A)
0.4
Fan Motor Horsepower (Hp)
1/8HP
Compressor Rated Load RLA (A)
15.7
Compressor Lock Rotor Amperage (LRA) (A)
86
Minimum Circuit Ampacity (A)
18.5
Breaker Size MIN/MAX (A)
20A/30A
Refrigerant Quantity (lbs)
R410A/3.417
Dry Weight (lbs)
134.5
Net Dimensions W×D×H (inches)
39.2×15.2×25.9
Water Pipe Connection
1.5 Inch Quick Connect
Water Proof Class
IPX4
Electricity Shock Proof Class
Refrigerant Side Pressure Limits (psi)
638/217
Water Side Pressure Limits (psi)
100 psi
The technical specifications of our heat pumps are provided for information purposes only. We
reserve the right to make changes without notice.
3. INSTALLATION