AM2020/AFP1010 Systems
PN 15842:K 7/23/2002 65
When in manual override mode, all points displayed on the ACM-24AT or
ACM-16AT and all its expanders will ignore subsequent Control-by-Event
(CBE) commands from the panel.
Manual Override Mode can be entered by pressing the Manual Override switch
on the ACM-24AT or ACM-16AT module (Use special slide-in label).
The Manual LED on the ACM-24AT or ACM-16AT module will
illuminate steadily.
The AM2020/AFP1010 will register an ANNUNCIATOR TROUBLE
condition.
The state of the each annunciator point will remain the same as before.
The output circuits can now be controlled via their point switches.
The AM2020/AFP1010 Control-By-Event will not override the
manual control setting of the ACM-24AT or ACM-16AT module. To
return the annunciator to Automatic Mode, press the Manual
Override switch again (toggle action). Set the DIP switches on a
Manual Override annunciator as follows.The switch numbers given
below are for SW28 on the ACM-24AT, and for the 8-pin DIP switch
on the ACM-16AT.
Dip Switch:
!
Switch
# ACM-24AT Function ACM-16AT Function
1 Manual override: Set “ON” for this application.
2, 3 Expanders installed: Set these switches according to how many expanders are
installed at the address. See Section 4.12.3 “Configuring Number of Expander
Modules” for ACM-24AT/ACM-48A; see Section 4.13.3 “Configuring Number of
Expander Modules” for ACM-16AT/ACM-32A.
4 Not used; set to OFF Eight-Point Shift: Always set this switch
“OFF” in AM2020/AFP1010 systems.
5 Receive Only: Set this switch “OFF” for this application.
6 Piezo Disable: Set this switch “ON” for this application unless the annunciator and
AMG-1 are not located adjacent to the AM2020/AFP1010. In that case, the piezo must
sound and the switch must be set to “OFF”.
7 Switch Inhibit: Set this switch “OFF” for this application.
8 Flash Inhibit: Set this switch “OFF” for this application.

Table of Contents

Other manuals for Notifier ACM-24AT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier ACM-24AT and is the answer not in the manual?

Notifier ACM-24AT Specifications

General IconGeneral
BrandNotifier
ModelACM-24AT
CategoryFire Alarms
LanguageEnglish

Related product manuals