AM2020/AFP1010 Systems
66 PN 15842:K 7/23/2002
P. 7 A C S P r o g r a m M a p p i n g
ACS points “track” or follow those system points they are programmed to
annunciate; the annunciator points do not latch. Table P-1, which follows, lists
how the ACS annunciates various devices and functions.
Note: Control Switches marked “not used” will still function as local LAMP TEST
switches for their respective LEDs.
1. In older systems, if the monitor module or XPM-8 circuit is programmed as a
supervisory point (SPSU), illumination of the trouble LED will occur for both
trouble and supervisory conditions. The exact status of the point (trouble versus
supervisory condition) can be read at the AM2020/AFP1010 control panel.
Prior to software release M2.8, supervisory points do not activate the point active
LEDs of an annunciator.
2. With the AM2020/AFP1010, the functions of ACK/STEP, SIGNAL SILENCE,
SYSTEM RESET and LAMP TEST may be assigned (mapped) to multiple
annunciator points.
Point Type
ACM-24AT or ACM-16AT Module and
AEM-24AT or AEM-16AT Expanders
ACM-48A or
ACM-32A Module &
AEM-48A or
AEM-32A Expander
Active LED Trouble LED Control Switch
Control Module
XPC Circuit
XPR Circuit
XPIQ Speaker and
Telephone/Strobe Circuits
Indicates on/off status
of module or circuit
Indicates trouble
status of module or
circuit
Turns module on/off
Monitor Module
XPM Circuit
XPIQ Monitoring
XP5-M
Indicates alarm status
of module or circuit
1
Indicates trouble
status of module or
circuit
1
Not used
Intelligent Detector Indicates alarm status
of detector
Indicates trouble
status of detector
Not used
Software Zone Indicates active status
of software zone
Indicates System
Trouble
Not used
ACK/STEP
1
Indicates System
Alarm
Indicates System
Trouble
ACK/STEP key
SIGNAL SILENCE
1
Not used Indicates Signals
Silence
SIGNAL SILENCE
key
SYSTEM RESET
2
Indicates System
Alarm
Indicates System
Trouble
SYSTEM RESET key
LAMP TEST
2
Not used Not used LAMP TEST key
Table P-1 Annunciator Program Mapping with AM2020/AFP1010