Nomenclature
7
Digital Operator
Data display
Keys
Indicators
(Setting/Monitor item
indicators)
FREQ adjuster
Appearance Name Function
Data display Displays relevant data items, such as frequency reference, output frequency,
and parameter set values.
Frequency adjuster Sets the frequency reference within a range between 0 Hz and the maximum
frequency.
Frequency reference
indicator
The frequency reference can be monitored or set while this indicator is lit.
Output frequency
indicator
The output frequency of the Inverter can be monitored while this indicator is
lit.
Output current
indicator
The output current of the Inverter can be monitored while this indicator is lit.
Multi-function
monitor indicator
The values set in U01 through U10 are monitored while this indicator is lit.
Forward/Reverse
selection indicator
The direction of rotation can be selected while this indicator is lit when
operating the Inverter with the RUN Key.
Local/Remote
selection indicator
The operation of the Inverter through the Digital Operator or according to the
set parameters is selectable while this indicator is lit. (See note 1.)
Parameter setting
indicator
The parameters in n01 through n79 can be set or monitored while this
indicator is lit. (See note 2.)
Mode Key Switches the setting and monitor item indicators in sequence.
Parameter being set will be canceled if this key is pressed before entering
the setting.
Increment Key Increases multi-function monitor numbers, parameter numbers, and
parameter set values.
Decrement Key Decreases multi-function monitor numbers, parameter numbers, and
parameter set values.
Enter Key Enters multi-function monitor numbers, parameter numbers, and internal
data values after they are set or changed.
RUN Key Starts the Inverter running when the 3G3JV is in operation with the Digital
Operator.
STOP/RESET Key Stops the Inverter unless parameter n06 is set to disable the STOP Key.
Used to reset the Inverter when an error occurs. (See note 3.)
Note: 1. The status of the local/remote selection indicator can be only monitored while the Inverter is in operation. Any RUN com-
mand input is ignored while this indicator is lit.
2. While the Inverter is in operation, the parameters can be only monitored and only some parameters can be changed. Any
RUN command input is ignored while the parameter setting indicator is lit.
3. For safety reasons, the reset function cannot be used while an operation instruction (forward/reverse) is being input. Turn
the operation instruction OFF before using this function.