I-66 Digital Controller E5CK
Specifications
■ Ratings
■ Input Ranges
Platinum Resistance Thermometer
Thermocouple
Note: Setting number is factory-set to 2 (K1).
Thermocouple W is W/Re 5-26 (tungsten rhenium 5, tungsten rhenium 26).
Current/Voltage
Item AC100-240V type AC/DC24V type
Supply voltage AC100 to 240V, 50/60 Hz AC/DC24V, 50/60 Hz
Power consumption 15 VA 6 VA, 3.5 W
Operating voltage range 85% to 110% of rated supply voltage
Input Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
Current input: 4 to 20 mA, 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, 1 to 10 V
Input impedance Current input: 150 Ω
Voltage input: 1 MΩ min.
Control output According to Output Unit (see “Output Unit Ratings and Characteristics”)
Auxiliary output SPST-NO, 1 A at 250 VAC (resistive load)
Control method ON/OFF or 2-PID control (with auto-tuning)
Setting method Digital setting using front panel keys
Indication method 7-segment digital display and LEDs
Other functions According to Option Unit (see “Option Unit Ratings and Characteristics”)
Input (switch selectable) JPt100 Pt100
Range °C −199.9 to 650.0 −199.9 to 650.0
°F −199.9 to 999.9 −199.9 to 999.9
Resolution (°C/°F)
(main setting and alarm)
01
Input (switch
selectable)
(see note)
K1 K2 J1 J2 T E L1 L2 U N R S B W PLII
Range °C −200
to
1,300
0.0 to
500.0
−100
to 850
0.0 to
400.0
−199.9
to 400.0
0 to
600
−100
to 850
0.0 to
400.0
−199.9
to 400.0
−200
to
1,300
0 to
1,700
0 to
1,700
100 to
1,800
0 to
2,300
0 to
1,300
°F −300
to
2,300
0.0 to
900.0
−100
to
1,500
0.0 to
750.0
−199.9
to 700.0
0 to
1,100
−100
to
1,500
0.0 to
750.0
−199.9
to 700.0
−300
to
2,300
0 to
3,000
0 to
3,000
300 to
3,200
0 to
4,100
0 to
2,300
Resolution (°C/
°F) (main setting
and alarm)
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Input (switch selectable) Current input Voltage input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Range One of following ranges depending on results of scaling
−1999 to 9999
−199.9 to 999.9
−19.99 to 99.99
−1.999 to 9.999
Resolution (°C/°F)
(main setting and alarm)
17 18 19 20 21