4 Safety Function Blocks
4 - 90
NX-series Safety Control Unit Instructions Reference Manual (Z931)
8311 33553 Muting Start 2 A muting sequence is being started after
MutingSwitch12 changed to TRUE. Monitoring is
active for DiscTimeEntry.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
8012 32786 Muting Active A muting sequence is in operation for one of the
following.
A change to TRUE was detected in the second
muting switch of S_MutingSwitch11 and
S_MutingSwitch12.
Both S_MutingSwitch11 and
S_MutingSwitch12 were started in the same
cycle.
Monitoring for DiscTimeEntry was stopped. Moni-
toring for MaxMutingTime was started.
Ready = TRUE
S_AOPD_Out = TRUE
S_MutingActive = TRUE
Error = FALSE
DiagCode (hexadecimal)
DiagCode
(decimal)
Status name Status description and output results