Regulations and standards
S8BA-24D24D□□□LF
18
Conformance to UL
This product must be installed within a control panel with an internal heater or other unit to protect
against the formation of condensation (Standard mounting only).
Gaps in the door to the control panel must be completely filled or covered with gaskets or other
material.
For use as a UL compliant device, the specifications for S8BA-24D24D480LF are as follows:
Maximum input current: 20A
Rated output current/capacity: 16.7A/400W
For use in Pollution Degree 2 Environment.
Surrounding Air Temperature, 55°C.
Make sure to connect the device with Class 2 output to the USB port.