5-1 Checking the battery
5 Maintenance and inspection
S8BA-24D24D□□□LF
73
5
3. Calculate the initial value of the backup time for the total capacity of the connected
devices from the graph below.
Graph of backup time (graph of initial values for products that have not been used
at 25°C). The backup time becomes shorter than the graph (table) below when
temperature is lower.
0
10
20
30
40
50
60
70
80
90
100
110
120
0 60 120
180 240
300 360
420 480
120W
240W
360W
480W
Capacity (W)
Backup time (Minutes)
The smaller the capacity of connected devices becomes, the longer the backup
time becomes.
Backup time table (Time unit: minutes)
Model
CapacityWatt)
30 60 90 120 180 240 300 360 420 480
120W 29 14 9 6
240W 58 29 19 15 9 6
360W 87 43 28 22 14 10 8 6
480W 119 59 39 29 19 15 11 9 8 6
*These backup times are for reference only. Times may vary according to battery life and
external environmental conditions (temperature, etc).