SINGLE THIMBLE DIAMETER
12”
(30s
mm)
LARGER
OR
DOUBLE VENTILATED THIMBLE
DIAMETER
6”
(
152
mm)
LARGER
INDOOR INSTALLATIONS
Locate exhaust outlet far from air inlet to avoid
recirculation. The engine exhaust is tapped for
1-1/2
inch thread. Use flexible tubing to connect theengine
exhaust to rigid pipe or muffler. Shield the line
if
it
passes through a combustible wall (Figure
4).
If turns
are necessary, use sweeping (large radius) elbows. If
pitched upward, install a condensation trap at point of
rise, Figure
5.
THANEXHAUS?
LINE
S
IN END
SLEEVE
EXHAUST LINE PASSING THROUGH
II
WALL OR PARTITION
FIGURE
4.
EXHAUST SHIELD
IF
EXHAUST LINE MUST BE PITCHED
UPWARD CONSTRUCT A TRAP OF PIPE
,.
FITTINGS AT POINT
OF
RISE
DRAIN CONDENSATION TRAP
PERIODICALLY
A617
FIGURE
5.
CONDENSATION TRAP
\WARNING)
ENGINE EXHAUST GAS (CARBON MONOXIDE) IS DEADLY!
Carbon monoxide is an odorless, colorless gas formed by incomplete
combustion of hydrocarbon fuels. Carbon monoxide is a dangerous gas that
can cause unconsciousness and is potentially lethal. Some of the symptoms or
signs of carbon monoxide inhalation are:
Dizziness Vomiting
Intense Headache
Weakness and Sleepiness
..
Muscular Twitching
Throbbing
in
Temples
If
you experience any of the above symptoms, get out into fresh air
immediately.
The best protection against carbon monoxide inhalation is a regular inspection
of the complete exhaust system.
If
you notice a change
in
the sound
or
appearance
of
exhaust system, shut the unit down immediately and have it
inspected and repaired at once by a competent mechanic.