EasyManuals Logo
Home>Panasonic>Air Conditioner>CS-A7DKD

Panasonic CS-A7DKD User Manual

Panasonic CS-A7DKD
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX1 at indoor electronic controller.
8.5. Operation Control
8.5.1. Restart Control (Time Delay Safety Control)
When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-
Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation.
Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.
If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operation
stop, although the unit is turn on again within the period.
This phenomenon is to balance the pressure inside the refrigerant cycle.
8.5.2. Compressor Reverse Rotation Protection Control
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C (cooling mode)/5°C (heating mode) or less for continuous 2 minutes, compressor will stop and
restart automatically.
Time Delay Safety Control is activated before the compressor restart.
s T = Intake air temperature - Indoor heat exchanger temperature
This is to prevent compressor from rotate reversely when there is an instantaneous power failure.
23
CS-A7DKD CU-A7DKD / CS-A9DKD CU-A9DKD / CS-A12DKD CU-A12DKD /

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-A7DKD and is the answer not in the manual?

Panasonic CS-A7DKD Specifications

General IconGeneral
BrandPanasonic
ModelCS-A7DKD
CategoryAir Conditioner
LanguageEnglish

Related product manuals