EasyManuals Logo
Home>PEERLESS>Boiler>ECT SERIES

PEERLESS ECT SERIES User Manual

PEERLESS ECT SERIES
19 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
WAYNE BURNER WITH 100 PSI PUMP PRESSURE
Boiler Burner Air Cone Nozzle Start-UpSettings
ModelNo, ModelNo, I,D, Size FlameLock Off-CycleDamp, Air Shutter
EC/ECT-03-075 HS 21/2" NoHoles .7580° A DEL 1 1.0 .50
EC/ECT-03-100 HS 21/2" NoHoles 1.0080" B DEL 1 1.2 1.50
EC/ECT-03-120 HS 21/2"NoHoles 1.2080° B DEL 11/2 1.5 1.75
EC/ECT-04-125 HS 21/2" 6 Holes 1.2580° B DEL 1 2.0 2.00
EC/ECT-04-150 HS 21/2" 6 Holes 1.5080° B DEL 3 2,0 2.25
EC/ECT-04-175 HS 21/2" 6 Holes 1.7580° B DEL 5 2,0 2.50
EC/ECT-05-175 HS 21/2" 6 Holes 1.7580° B DEL 5 2.0 2.50
EC/ECT-05-200 HS 21/2" 6 Holes 2.00 80° B DEL 5 2,0 3.50
EC/ECT-05-250 HS 21/2" 6 Holes 2.50 80° S DEL 8 2.0 5.00
EC/ECT-06-275 HS 3-5/16" Str.Bore 2.75 80° B DEL 2 2,0 4.00
EC/ECT-06-300 HS 3-5/16'` Str.Bore 3.00 80° B DEL 2 2.0 4.50
CARLIN BURNER
Boiler Burner Start-UpSettings
ModelNo. ModelNo. Air Shutter NozzleSize PumpPressure HeadDim.A Air Band
EC/ECT-04-125 *99FRD Blank 1.00x 70° B DEL 150 PSI 2 40%open
EC/ECT-04-150 *99FRD Blank 1.25x 60° B DEL 150 PSI 3 60%open
EC/ECT-04-175 *99FRD Blank 1,50x 60° B DEL 150 PSI 4 100%open
EC/ECT-05-175 *99FRD Open 1,50x 60° B HAGO 150 PSI 5 10%open
EC/ECT-05-200 *99FRD Open 1,65x 60° B HAGO 150 PSI 5 45%open
EC/ECT-05-250 *99FRD Open 2,00 x 60° B HAGO 150 PSI 8 100%open
EC/ECT-06-275 102CRD Open 2,75x 60° B DEL 100 PSI 7 100%open
EC/ECT-06-300 102CRD Open 3,00x 60° B DEL 100 PSI 9 100%open
*Model99FRDBurnerEquippedwithModel98022PSCMotor
CARLIN EZ-IHP OILBURNERWITHMODEL98022PSC MOTOR
Boiler Burner Start-UpSettings
ModelNo, FiringRate ModelNo, AirShutter NozzleSize PumpPressure AirBand HeadBar
EC/ECT-03-075 .75 EZ-1HP Blank 0.60 x70° B DEL 150 PSI 0.55 0.60- 0.65
EC/ECT-03-100 1.00 EZ-1HP Blank 0.85 x70° A DEL 150 PSI 0.65 0.85- 1.00
EC/ECT-03-120 1.20 EZ-1HP Blank 1.00 x70° A DEL 150 PSI 0.80 0,85- 1.00
BECKETTBURNERWITH140 PSIPUMPPRESSURE
Boiler Burner Burner Static Nozzle Start-UpSettings Head
ModelNo. ModelNo. Head Plate Size AirShutter AirBand Setting
AFG-LI* LI* 33/8" .6560" B HAGO 9.0 2 N/A
AFG-L1 L1 33/8" .8560° B HAGO 10.0 1 N/A
AFG-L1 L1 ** 1.0060° B HAGO 9.0 2 N/A
AFG-F6 F6 23/4" 1.1080° A DEL 5.0 1 N/A
AFG-F6 F6 23/4" 1.2580° B HAGO 8.0 1 N/A
AFG-F6 F6 23/4" 1.5080° B HAGO 10,0 3 N/A
AFG-MV1 M-V1-3 -- 1.5060° B HAGO 10.0 3 3
AFG-MV1 M-V1-3 -- 1.7560° B HAGO 10,0 9 3
AFG-MV1 M-V1-5 -- 2.00 45° BHAGO I 0.0 5 5
CF-375 L1-S -- 2.25 450P HAGO 10.0 6 2
CF-375 L1-S -- 2.50 45° P HAGO 10.0 6 3
EC/ECT-03-075
EC/ECT-03-100
EC/ECT-03-120
EC/ECT-04-125
EC/ECT-04-150
EC/ECT..04-175
EC/ECT..05-175
EC/ECT,.05-200
EC/ECT..05-250
EC/ECT..06-275
EC/ECT-06-300
* RequiresLowFiringRateBaffle ** Removestaticplatefor 1.20GPHrate.
NOTE:Aboveair settingsare start-upsettingsonly-- final adjustmentsare to bemadewithcombustiontest instruments.Adjustburnerfor
highestCO2 (Maximum13%)whilemaintaininga 0 smokeand -.01to -.02ovediredraft.
Figure7 (continuedon nextpage)
8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PEERLESS ECT SERIES and is the answer not in the manual?

PEERLESS ECT SERIES Specifications

General IconGeneral
BrandPEERLESS
ModelECT SERIES
CategoryBoiler
LanguageEnglish

Related product manuals