Maintenance • Troubleshooting 11
Troubleshooting
Symptom Possible Cause(s) Corrective Action(s)
Motorwillnotrun
Disconnect switch is off Besureswitchison.
Fuse is blown or circuit breaker
tripped.
Replace fuse or reset circuit breaker.
Starting switch is defective. DISCONNECTPOWER;Replacestartingswitch.
Wires at motor are loose,
disconnected, or wired incorrectly.
Refertoinstructionsonwiring.DISCONNECTPOWER;checkandtightenallwiring.
Risk of electrical shock. Capacitor voltage may be hazardous. To
dischargecapacitor,holdinsulatedhandlescrewdriverBYTHEHANDLEandshort
capacitor terminals together. Do not touch metal screwdriver blade or capacitor
terminals. If in doubt, consult a qualified electrician.
Motorrunshotandoverloadkicks
off.
Motoriswiredincorrectly. Refer to instructions on wiring.
Voltageistoolow
Check with power company. Install heavier wiring if wire size is too small (See
Electrical/WiringChart).
Motorrunsbutnowaterisdelivered
in new installation:*
1. Improper priming 1. Re-prime according to instructions.
2. Air leaks 2. Check all connections on suction line, with soapy water or shaving cream.
3.Leakingfootvalveorcheck
valve
3. Replace foot valve or check valve.
Pump has lost prime in installation
already in use:
1. Air leaks 1. Check all connections on suction line and shaft seal.
2. Water level below suction pipe
inlet
2.Lowersuctionlineintowaterandre-prime.Ifrecedingwaterlevelinwellexceeds
20’(6.1M),adeepwellpumpisneeded.
Foot valve or strainer is plugged Clean foot valvye or strainer.
Impeller is plugged Clean impeller.
Check valve or foot valve is stuck
shut
Replace check valve or foot valve.
Pipes are frozen Thawpipes.Burypipesbelowfrostline.Heatpitorpumphouse.
Foot valve and/or strainer are
buried in sand or mud.
Raise foot valve and/or strainer above bottom of water source. Clean foot valve and
strainer.
Water level is too low for shallow
well setup to deliver water.
Pumpwillnotliftwatermorethan20’(6.1M).
Pump does not deliver water to full
capacity.
Water level in well is lower than
estimated.
Adeepwelljetwillbeneededifdepthtowaterinyourwellismorethan20’
(6.1m).
Steel piping (if used) is corroded
or limed, causing excess friction.
Replace with plastic pipe where possible, otherwise with new steel pipe.
Piping is too small in size Uselargerpiping.
Packed well point Backflushwellpointorsinknewpoint.
*Stoppump;thencheckprime
before looking for other causes.
Unscrewprimingplugandseeif
water is in priming hole.
8. Reinstall the sleeve on the bracket and the pump
suctionbodyinthesleeve.Besurethatyoudonot
pinch or damage the O-Ring. See Figure27.
9. Installfourcapscrews(Ref.No.18)throughthe
pump head and into the bracket. Tighten the
capscrews to 22ft.-lbs. torque.
10. Reinstallthedrainplugandwasher(Ref.Nos.17
and 16) in the suction body.
NOTICE: Do not disturb the recirculation valve.
11. Reinstall the suction and discharge piping and open
all valves. Check for leaks.
12. Prime the pump according to the instructions on
Page 8.
Recirculation Valve
Do not disturb!
Figure 27
Figure 26