onlinecomponents.com
Appendix A
6057AC01 A-1
A Technical Appendix
A 1 Installation Local Bus Cables
Table A-1 Specifications for installation local bus cables
a
IBSL SLC CU2/1,5-METER IBSL PSC CU3/1,5-METER
Order No. 27 21 62 0 27 22 13 7
Application Installation local bus/sensor
supply (indoor installation)
Actuator supply (indoor
installation)
Structure 2 single conductors with
common outer sheath, twisted,
unshielded
3 single conductors with
common outer sheath,
unshielded
Color coding of the wires DIN 47100
Brown, blue
DIN 47100
Brown, blue, green/yellow
Conductor size 1.5 mm² (16 AWG)
Outside diameter 7.5 mm (0.295 in.) 8.4 mm (0.331 in.)
Outer cable sheath Green
RAL 6017
Special mixture on PVC base
Black
RAL 9005
Special mixture on PVC base
Operating temperature Fixed
-30°C to +70°C (-22°F to +158°F)
Bending radius Fixed at least 8 x D
(60 mm [2.362 in.], minimum)
Fixed at least 8 x D
(67.2 mm [2.646 in., minimum])
Test voltage wire-wire U
rms
= 1000 V, 1 min
(VDE 0472-509, test type C, IEC 60189 cl. 5.2)
Conductor resistance 13.3
W/km, maximum
(VDE 0295)
Isolation resistance (after
testing the dielectric
strength)
20 M
W/km, minimum
(VDE 0472-502, test type B, ICE 60189-1 cl. 5.3)
Characteristic impedance 75
W ±5%
at f = 250 kHz to 10 MHz
(IEC 61156-1 cl. 3.3.6)
–