1.10 Common Technical Data
The technical data does not claim to be complete. Phoenix Contact
reserves the right to make any technical changes that serve the purpose of
technical progress.
Ambient Conditions
Regulations Developed according to VDE 0160, UL 508
Ambient temperature Operation: -25°C to +70°C (-13°F to +158°F)
(These values are not valid for all INTERBUS
Loop modules. For the exact values please refer
to the module-specific data sheets.)
Storage/transport: -40°C to +85°C
(-40°F to +185°F)
Humidity (I/O modules) Operation: 100% (no condensation)
Storage/transport: 95% (no condensation)
Air pressure Operation: 80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level)
Storage/transport: 66 kPa to 106 kPa
(up to 3500 m [11483 ft.] above sea level)
Degree of protection IP 65/IP 67: I/O modules, BK modules
IP 20: BK modules
IP 54: Motor starters
(IEC 60536)
Class of protection Class 3 according to VDE 0106, IEC 60536, use
power supplies with safe isolation
Air and creepance distances According to IEC 60644/ IEC 60664A/
DIN VDE 0110: 1989-01 and
DIN VDE 0160: 1988-05
Housing material (INTERBUS Loop modules,
IP 20 BK module)
Polyamide 6.6 V0, self-extinguishing (V0)
Vibration test 5g, 10 Hz to 150 Hz, (IEC 60068-2-6)
(Acceleration amplitude above the limit
frequency)
Shock test 15g (IEC 60068-2-27)