- 31 -
GB
4.10 Parameters
Press Key to switch off the machine, it is possible to change the SetPoint, by simultaneously pressing, for five
seconds, Key and Key
• Display1 shows the parameter value.
• Display2 shows the number of parameters in blink mode ’01’.
• Display3 shows the letter ‘P’ in blink mode.
Select the parameter through key and .
Press key to change the Parameter:
• Display1 shows the selected parameter value in blink mode.
• Display2 shows the number of parameters ’15’.
• Display3 shows the letter ‘P’.
Press key and to change the parameter values.
Press Key to confirm the new Parameter value, the system then returns to Parameter selection.
Exit from the Parameter menu takes place automatically after a TimeOut of 60 seconds, or can be obtained manually by
pressing Key .
Parameter Description Default min MAX
P01 Differential for the high temperature alarm to get back +2°C 0°C +10°C
P02 Alarm threshold for high temperature in chilling conservation +7°C 0°C +50°C
relating Set CONS
P03 Alarm value for low temperature in chilling conservation 0°C -10°C 0°C
P04 Alarm treshhold for high temperature in freezing conservation +6°C 0°C +50°C
relating Set CONS
P05 Alarm treshhold for low temperature in freezing conservation -10°C -50°C +10°C
relating Set CONS
P06
Temperature alarm delay from conservation start or defrosting process
60min 0min 300min
P07 Temperature alarm delay in cilling/freezing conservation 30min 0min 300min
P08 Delay for power failure alarm 2min 0min 300min
P10 Temperature measurement unit (1= Celsius; 0= Fahrenheit) 1 0 1
P11 Cold room probe offset 0°C -10°C +10°C
P12 Polarity with open door 0 0 1
0: DI closed = Closed door
1: DI closed = Open door
P13 Open door alarm delay 2 min 0 min 60 min
P14
P15 Buzzer activation ( 0 = not enabled; 1= enabled ) 1 0 1
P16 Buzzer duration at the end chilling/freezing cycle 10 sec 0 600 sec
P17 Buzzer duration in alarm status 1 min 0 min 90 min
P18 Core probe recognition 1(Frc)/ 0 1
0 = Manual 1 = Automatic 0 (Hr)
P20 Auxiliary relay use 1 0 1
0 = Lighting 1 =Remote Alarm
P21 Cycles type activation: 0 0 1
0= chilling +freezing
1 = chilling only
P22 Safety devices alarm delay 5 sec 0 sec 60 sec