24V, 3.4A, SINGLE PHASE INPUT
Jul. 2020 / Rev. 2.3 DS-QS3.241-EN
All parameters are specified at 24V, 3.4A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
26/26
22.13. MOUNTING ORIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature. The amount of reduction
influences the lifetime expectancy of the power supply. Therefore, two different derating curves for continuous
operation can be found below:
Curve A1 Recommended output current.
Curve A2 Max allowed output current (results in approximately half the lifetime expectancy of A1).
Fig. 23-7
Mounting
Orientation A
(Standard
orientation)
Output Current
0
10 20 30 40
60°C
0.7
2.1
2.8
3.5A
50
A1
1.4
Ambient Temperature
Fig. 23-8
Mounting
Orientation B
(Upside down)
Output Current
0
10 20 30
40 60°C
0.7
2.1
2.8
3.5A
50
1.4
A1
A2
Ambient Temperature
Fig. 23-9
Mounting
Orientation C
(Table-top
mounting)
Output Current
0
10 20 30 40
60°C
0.7
2.1
2.8
3.5A
50
1.4
A1
A2
Ambient Temperature
Fig. 23-10
Mounting
Orientation D
(Horizontal cw)
Output Current
0
10 20 30 40
60°C
0.7
2.1
2.8
3.5A
50
1.4
A1
A2
Ambient Temperature
Fig. 23-11
Mounting
Orientation E
(Horizontal ccw)
Output Current
0
10 20 30 40
60°C
0.7
2.1
2.8
3.5A
50
1.4
A1
A2
Ambient Temperature