Revision 1.1 Page 17 of 21
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mobile Controller User Guide
www.resourcedm.com
Fans Only “FAnS”
Selecting the Fans Only option will put the controller into the Fans Only state if the current state is not Fans Only. If the current state is
Fans Only then the controller will change to the Normal state. Selecting this option will exit the setup menu automatically. The display will
show “FAnS OnLy”
If a remote display with key switch is being used, this function can be invoked by turning the key switch to the fans only position (90
degrees clockwise) with parameter P85 set to "fans"
Case Off “CASE”
Selecting the Case Off option will put the controller into the Case Off state if the current state is not Case Off. If the current state is Case
Off then the controller will change to the Normal state. Selecting this option will exit the setup menu automatically. The display will show
“CASE OFF”. An alarm is generated, fixed delay of 1 minute, when the controller is placed into the Case Off state.
If a remote display with key switch is being used, this function can be invoked by turning the key switch to the case-off position.
(Clockwise 90 degrees) with parameter P85 set to "case".
Lights Only “Ligt”
Selecting the Lights Only option will put the controller into the Lights Only state if the current state is not Lights Only. If the current state is
Lights Only then the controller will change to the Normal state. Selecting this option will exit the setup menu automatically. The display
will show “LitS OnLy”
Note. When lights are being used in “Remote” mode with a timing channel: -
If the controller goes offline, the lights are turned ON after a delay of 5 minutes. The lights will stay on until the controller comes back on-
line where they will revert to the state of the timing channel being used.
Probe Offset
This feature allows each probe value to be modified by an “offset”. Offset values are from -10
O
C (-18
O
F) to +10
O
C (+18
O
F) and on a
channel basis. Example C1 = Probe 1.
Remote Commands
The following commands can be used by a Data Builder program: -
Command
Value to send
Description
Conditions
Defrost Command
1
Initiates a defrost cycle
Defrost mode: remote
Defrost Command
3
Terminates the defrost
Defrost mode: remote
Defrost hold: On
Defrost min state complete
Setpoint Command
+/-18
Is added to or subtracted from the setpoint
Case Off Command
5
0
Sets the controller to Case Off
Restores the controller from Case Off to Normal
Haccp Command
0
1
2
HACCP LED OFF
HACCP LED On
HACCP LED Flashes
Button Command
0
1
2
Buttons backlights Off
Buttons backlights On
Buttons Backlights Flash

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Resource Data Management PR0750-MOB and is the answer not in the manual?

Resource Data Management PR0750-MOB Specifications

General IconGeneral
BrandResource Data Management
ModelPR0750-MOB
CategoryController
LanguageEnglish

Related product manuals