Revision 1.1 Page 18 of 21
Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Ensure that all power is
switched off before
installing or maintaining
this product
Mercury 2 & Intuitive Mobile Controller User Guide
Specification
Warning: Relay 5 output has hazardous voltages (Supply input voltage potential)
This does not apply to the Intuitive Mercury controller
Mercury Mk2 Controller
PR0710-MOB & PR0720-MOB
Intuitive Mercury controller
PR0750-MOB & PR0760-MOB
5.2 Amps (when relay 5 is fully loaded)
Operating temperature range
Storage temperature range
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
Indoor use at altitudes up to 2000m, pollution
degree 1, installation category II. Voltage
fluctuations not to exceed ±10% of nominal
voltage.
78mm (W) x 36mm (H) x 110mm (D)
157mm (W) x 67mm (H) x 120 (D)
EN61326; 1997 +Amdt. A1; 1998
EN61326; 1997 +Amdt. A1; 1998
There is no requirement for forced cooling
ventilation
There is no requirement for forced cooling
ventilation
No protective Earth is required and none
should be fitted
No protective Earth is required and none should
be fitted
The host equipment must provide a suitable
external over-current protection device such
as: -
Fuse: 6.3A 240 Vac Antisurge (T) HRC
conforming to IEC 60127
Built in fuse holder, fuse 2A 240Vac Antisurge (T)
HRC conforming to IEC60127, 32 x 6.3mm
6A, 240 VAC Type C conforming to BS EN
60898
2A, 240 VAC Type C conforming to BS EN 60898
(Note: controller has integral 2A fuse)
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relays 1-4 Mechanical Type (M)
Exclusive common
6A Resistive (CosØ = 1)
2A Inductive ( CosØ = 0.4)
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
10A 240Vac Antisurge (T) HRC conforming to
IEC60127, 32 x 6.3mm
Relay 5 Mechanical Type (M)
Common connected to supply
live
Relay 5 Mechanical Type (M)
Exclusive common
3A (non inductive), COS=0.4 2A (inductive
load) 200,000 operations
10A Resistive (CosØ = 1)
3A Inductive ( CosØ = 0.4)
250Vac. 30V dc (external supply)
For compliance with the LVD, relays 3, 4 and 5
commons must be at the same potential as the
supply voltage
All relays are independent and can operate at
different potentials to the supply voltage.