Inverter module temperature: displays the IGBT module temperature. Different
model has different IGBT over-temperature threshold.
Inverter software version: DSP embedded software version.
Accumulative running time: displays the accumulative running time as the VFD
has recorded.
Accumulative power-on time: displays the accumulative power-on time as the
VFD has recorded.
5.9 F8 Group Auxiliary Function Parameters
F8.00
Jog running frequency Factory Setting 5.00Hz
Setting Options 0.00~F0.10
F8.01
Jog running acceleration
time
Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
F8.02
Jog running deceleration
time
Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s
These parameters define the jogging frequency, acceleration and deceleration time.
The jogging procedure is according to start mode F1.00=0(Start directly) and Stop
mode F1.05=0(Decelerate to stop).
Jog running acceleration time is the interval time for the VFD to accelerate from
0Hz to max. output frequency(F0.10).
Jog running deceleration time is the interval time for the VFD to decelerate from
max. output frequency(F0.10) to 0Hz.
F8.03
Acceleration time 2 Factory Setting
Defined by
inverter model
Setting Options 0.1~3600s