Samsung Electronics
2-3 Combination and Connection Ratio limitation
Outdoor unit
Cooling
capacity (kW)
Maximum allowable
connections for indoor units
(Not including Hydro-A2W)
Total capacity of
connected indoor units
(kW)
AE044MXTPEH
4.4 2 2.2~4.4
AE066MXTPEH
6.6 3 3.3~6.6
AE090MXTPEH
9 4 4.5~9.0
AE120MXTPEH
12 5 6.0~12.0
AE160MXTPEH
16 7 8.0~16.0
AE090MXTPGH
9 4 4.5~9.0
AE120MXTPGH
12 5 6.0~12.0
AE160MXTPGH
16 7 8.0~16.0
• Available for max 7 indoor units.
• When considering the system capacity of allowable indoor units, follow the table above.