74 Samsung Electronics
3-35. Outdoor unit’s option switch setting error.
(Using E2P option of other models or emergency operation for compressor malfunction
option setting was enabled on all compressors of corresponding outdoor unit) (E-560)
Outdoor unit Display E-560
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem
t0QUJPOTFUUJOHFSSPSPGPVUEPPSVOJU
(E2P option use of other model or set of the relevant outdoor unit, compressor
breakdown)
Is the Compressor
breakdown setting value is
“not set”?
Is the outdoor unit
EEPROM accurately connected to
connector?
Download relevant model EEPROM and then reset.
Execute automatic commissioning for UP
cancellation after EEPROM download
Set the compressor breakdown setting value as“not set.
ఐWhen setting breakdown for repair and replace
of compressor : Change the setting after replace.
Connect outdoor unit EEPROM and then reset.
Yes
No
Yes
No