EasyManuals Logo
Home>Sanyo>Air Conditioner>STW0923C2

Sanyo STW0923C2 User Manual

Sanyo STW0923C2
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
6. ELECTRICAL DATA
6-1. Electrical Characteristics
COOLING
Model Number : STW0622C2 / 0623C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 / 208V, 1-phase 60Hz
Rating conditions Running amps. A 0.11 / 0.10 0.37 / 0.36 2.22 / 2.44 2.7 / 2.9
Power input kW 0.025 / 0.020 0.085 / 0.075 0.500 / 0.505 0.61 / 0.60
Full load conditions Running amps. A 0.11 / 0.10 0.37 / 0.36 2.82 / 3.04 3.3 / 3.5
Power input kW 0.025 / 0.020 0.085 / 0.075 0.630 / 0.635 0.74 / 0.73
Model Number : STW0922C2 / 0923C2 / 0925C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 / 208V, 1-phase 60Hz
Rating conditions Running amps. A 0.11 / 0.10 0.37 / 0.36 3.02 / 3.34 3.5 / 3.8
Power input kW 0.025 / 0.020 0.085 / 0.075 0.690 / 0.685 0.80 / 0.78
Full load conditions Running amps. A 0.11 / 0.10 0.37 / 0.36 3.82 / 4.14 4.3 / 4.6
Power input kW 0.025 / 0.020 0.085 / 0.075 0.870 / 0.855 0.98 / 0.95
Model Number : STW1222C2 / 1223C2 / 1225C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 / 208V, 1-phase 60Hz
Rating conditions Running amps. A 0.17 / 0.17 0.43 / 0.43 4.30 / 4.80 4.9 / 5.4
Power input kW 0.040 / 0.035 0.100 / 0.090 0.960 / 0.965 1.10 / 1.09
Full load conditions Running amps. A 0.17 / 0.17 0.43 / 0.43 5.50 / 6.20 6.1 / 6.8
Power input kW 0.040 / 0.035 0.100 / 0.090 1.240 / 1.235 1.38 / 1.36
Model Number : STW1522C2 /1523C2 / 1525C2
Indoor Unit Outdoor Unit Complete Unit
Fan Motor Fan Motor Compressor
Performance at 230 / 208V, 1-phase 60Hz
Rating conditions Running amps. A 0.17 / 0.17 0.43 / 0.43 6.30 / 6.60 6.9 / 7.2
Power input kW 0.040 / 0.035 0.100 / 0.090 1.350 / 1.335 1.49 / 1.46
Full load conditions Running amps. A 0.17 / 0.17 0.43 / 0.43 8.00 / 8.40 8.6 / 9.0
Power input kW 0.040 / 0.035 0.100 / 0.090 1.720 / 1.705 1.86 / 1.83
Rating Conditions : Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 95F (35°C) D.B.
Full Load Conditions : Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.
Outdoor Air Temperature 115°F (46.1°C) D.B.
Cooling & electric heating models (230/208 V)