10. FUNCTION
10-1. Room Temperature Control
Room temperature control is obtained by cycling the compressor ON and OFF.
Cooling
Once the compressor stops, it will not start running again for about 3 minutes (*).
(*) Actual compressor OFF time indicated by "3 minutes" varies between 2 minutes 45 seconds to 4 minutes.
Thermo. ON : When the room temperature rises above T + 1°F (T°F is set temperature).
Compressor
ON
Thermo. OFF : When the room temperature falls below set temperature T°F (T°F is set temperature).
Compressor
OFF
Heating
Heater ON : When the room temperature falls below T°F (T°F is set temperature).
Heater
ON
Heater OFF : When the room temperature rises above T + 1°F (T°F is set temperature).
Heater
OFF
Room temp.
T °F
T+1°F
Heater
ON
ON
OFFOFF OFF OFF
ON
Room temp.
T °F
T+1°F
Compressor
ONON
ON
OFF OFF
3 minutes
Within
3 minutes
3 minutes
or more
NOTE
Cooling & Electric Heating Models